Distinguishing, judging and solving methods of three-phase voltage imbalance


There are many reasons for three-phase voltage imbalance, such as single-phase grounding, broken line resonance, etc. Only by correctly distinguishing them can the operation management personnel quickly deal with them.

1、 Disconnection fault If one phase is disconnected but not grounded, or one phase of the circuit breaker and disconnector is not connected, the fuse of the Voltage transformer is blown, which will cause three-phase parameter asymmetry. When one phase of the line at the previous voltage level is disconnected, the voltage of the next voltage level shows that the voltage of three phases is reduced, one phase is low, and the other two phases are high, but their voltage values are close. When this level of line is disconnected, the phase voltage of the disconnected line is zero, and the phase voltage of the unbroken line is still the phase voltage.

2、 Ground fault When one phase of the line is disconnected and the single phase is grounded, although it causes three-phase voltage imbalance, the voltage value does not change after grounding. Single phase grounding is divided into two types: metallic grounding and non-metallic grounding. Metal grounding, with zero or near zero fault phase voltage, and a 1.732 fold increase in non fault phase voltage, which remains unchanged for a long time; Non metallic grounding, the voltage of the grounding phase is not zero but decreases to a certain value, and the other two phases increase by less than 1.732 times.

3、 Resonance causes With the rapid development of industry, nonlinear power loads have increased significantly. Some loads not only produce harmonics, but also cause supply voltage fluctuations and flickers, and even cause three-phase voltage imbalance.

There are two types of three-phase voltage imbalance caused by resonance

One type is fundamental frequency resonance, which is similar to single-phase grounding, where one phase voltage decreases and the other two phases voltage increases. It is difficult to find the fault point when searching for the cause of the fault. At this time, special users can be checked. If it is not due to grounding, it may be caused by resonance.

The other is frequency division resonance or high-frequency resonance, which is characterized by simultaneous rise of three-phase voltage.

In addition, it should be noted that when the air drop bus cuts off part of the line or the single-phase grounding fault disappears, if there is a grounding signal and the voltage of one phase, two phases or three phases exceeds the line voltage, the pointer of the Voltmeter will reach the end and move slowly at the same time, or the three-phase voltage will rise in turn to exceed the line voltage, which is generally caused by resonance.

The harm and impact of three-phase imbalance

1. Hazards to transformers. In production and daily electricity consumption, when the three-phase load is unbalanced, the transformer is in an asymmetric operating state. Causes an increase in transformer losses (including no-load losses and load losses). According to the transformer operation regulations, the neutral line current of the transformer during operation shall not exceed 25% of the rated current on the low-voltage side of the transformer. In addition, unbalanced operation of three-phase loads can cause excessive zero sequence current in transformers, increase the temperature of local metal parts, and even lead to transformer burnout.

2. Impact on electrical equipment. The occurrence of three-phase voltage imbalance will lead to several times of current imbalance. Induce an increase in reverse torque in the electric motor, resulting in an increase in temperature, a decrease in efficiency, an increase in energy consumption, vibration, and output losses. The imbalance between different phases can shorten the service life of electrical equipment, accelerate the frequency of component replacement, and increase the cost of equipment maintenance. The circuit breaker allows for a reduction in the residual current, which can easily cause overloading and short circuits when the load changes or alternates. Excessive unbalanced current flows into the neutral wire, causing it to become thicker.

Related news


Distinguishing, judging and solving methods of three-phase voltage imbalance

There are many reasons for three-phase voltage imbalance, such as single-phase grounding, broken line resonance, etc. Only by correctly distinguishing them can the operation management personnel quickly deal with them.


Using SVR Line Automatic Pressure regulator to Solve the Low Voltage Problem of 10kV Line

The current measures taken to address the issue of "low voltage" in rural power grid lines mainly include the following: the cross-sectional area of newly constructed wires; Adjust the main transformer tap of the substation to change the system voltage; Reasonably distribute reactive power compensation equipment in the system to improve the distribution of reactive power flow in the power grid; Transform the line and increase the load of the pump station; Increase the number of outgoing lines in the substation to share the load of the original line. The above measures have the following issues.


Three Major Trends in the Development of Intelligent Terminal Distribution Industry and Technology

In recent years, the distribution industry in China has developed rapidly. In addition to strictly adhering to engineering standards, designers also need to continuously deepen their understanding and mastery of new trends in intelligent equipment and technology in order to ensure that they can provide high-quality products while meeting the increasingly strict needs of customers to a large extent. Based on my over 20 years of professional design experience in the distribution industry, intelligent terminal distribution systems can only become a benchmark product in the industry and lead the development direction of the future distribution industry by making breakthroughs in safety, diversity, and innovation.


Prospects for the Development of China's Electrical Industry

In this year of the beginning of the 12th Five Year Plan, for the electrical industry, power grid construction will become the focus of power investment in 2011. At the same time, related smart grid construction, rural power grid transformation, and ultra-high voltage power grid construction have once again encountered significant opportunities for rapid development in this era.


The sales market of high and low voltage electrical appliances in China is mainly in China

With the obvious acceleration of investment in new energy industry, high-tech industry, advanced equipment manufacturing industry and real estate development, and the increasing demand for industrial distribution automation and civil distribution intelligence, the market prospect of complete sets of high and low voltage electrical equipment is broad.


Thoroughly dissect and decompose the detailed structure of three-phase asynchronous motors

A three-phase asynchronous motor consists of two basic parts: a fixed stator and a rotating rotor. The rotor is installed in the stator cavity and supported on two end covers by bearings. In order to ensure that the rotor can rotate freely within the stator, there must be a gap between the stator and the rotor, called an air gap. The air gap of an electric motor is a very important parameter, and its size and symmetry have a significant impact on the performance of the motor.