  • 23-min.png

Switch vacuum tester ZKZ2-S169

It is used for the quality control of the arc extinguishing chamber in the vacuum arc extinguishing chamber production line and the inspection of the arc extinguishing chamber of the circuit breaker manufacturer. This type of tester with a fixed coil

Classification:

High voltage switch performance test instrument


Product description

Instrument Usage

• It is used for the quality control of the arc extinguishing chamber in the vacuum arc extinguishing chamber production line and the inspection of the arc extinguishing chamber of the circuit breaker manufacturer. This type of tester is equipped with a fixed coil.

• Used to detect the vacuum degree of the vacuum interrupter installed on the switch machine. This type of testing is mainly used for routine maintenance and capacity testing of the power supply sector to determine the capacity of the vacuum interrupter, this type of tester with a detachable coil.

 

performance characteristics

• sampling technology based on ionization charge

vacuum tester adopts sampling technology based on ionization charge. In the study of magnetron discharge, experts from our company found that when the external excitation power supply, the geometric size of the vacuum interrupter and the materials used are certain, the vacuum degree in the vacuum interrupter has a very accurate correspondence with the amount of ionized charge, while the peak value of the ionization current has only a probabilistic correlation. Therefore, our company pioneered the sampling technology based on ionization charge, which significantly improved the accuracy of the vacuum measurement of the vacuum interrupter.

• Leakage Current Treatment

When high voltage is applied to both ends of the vacuum interrupter in the breaking state, there will be several microamperes of leakage current with different values. Even the vacuum interrupter of the same type has large individual differences. Especially for the vacuum interrupter installed on the whole machine, due to its peripheral insulating support also has leakage, the sum of these leakage has greater instability and unpredictability, and the value is equivalent to the ionization current of the vacuum interrupter of the order of 10E-4Pa. We use the method of starting high voltage twice, deducting the leakage current, and ensuring the vacuum metering accuracy of the vacuum interrupter, whether it is installed on the whole machine or to be installed.

• Judge the vacuum interrupter with complete air leakage

Judge whether the vacuum interrupter is completely air leakage by means of high voltage breakdown.

• PC controls the measurement, calculates the leakage rate, and forms the measurement database

. This part is optional. Through the interface, the tube type, current or vacuum degree, the database used by the setting, by the PC control of the entire measurement process, display the measurement results and the data stored in the whole time of the specified database. After two measurements of the same vacuum interrupter, the leakage rate can be calculated by interface control.

• Built-in measurement curve of almost all vacuum interrupter at home and abroad

vacuum interrupter due to its different geometric size and materials, when the internal vacuum degree and external excitation power supply are constant, its discharge charge is different, and there are considerable differences. For accurate measurement, each vacuum interrupter must have a corresponding calculation curve from the amount of ionized charge to the vacuum degree. Our company's experts through close cooperation with the main domestic vacuum interrupter manufacturers, made almost all of the domestic and foreign vacuum interrupter ionization charge and vacuum degree of the relationship between the data, through mathematical processing, the characteristic parameters into the product. Therefore, the product has built-in measurement curves of almost all vacuum interrupters at home and abroad. This is unique among similar products at home and abroad.

• Perfect input protection circuit

When the vacuum degree of the vacuum interrupter is very low, the vacuum interrupter will be broken down by high voltage during measurement, and the instantaneous high voltage will be directly applied to the sampling circuit at the signal input end to make it bear very strong electric impact. The sampling circuit of the signal input terminal of the ZKZ2-S169 adds a complete protection circuit, even if the instrument temporarily works abnormally due to the high voltage impact of the input terminal (restart), it will not cause damage to the circuit part.

 

Technical Parameters

• Measurement Range: 1 × 10-5~1 × 10-1Pa

• Measurement Error: 1 × 10-4~1 × 10-1 Pa median error <10%

• measurement resolution: 10-5Pa

• electric breakdown will occur in the leaking arc extinguishing chamber during measurement.

• allowable ring temperature: 0 ℃ ~ 55 ℃

• air humidity: <85% RH

• power supply: AC 220 10%

• external dimensions: 455x 330x 250mm out.